Mob:86-13598063647   Whatsapp: 86-13271592250

Zhengzhou Wubai Cable and Wire Co.,Ltd

KC/KX/SC fiberglass/silicone/telfon/PVC thermocouple compensation/extension cable/wire

    KC/KX/SC fiberglass/silicone/telfon/PVC thermocouple compensation/extension cable/wire
DETAILS
 

thermocouple compensation cable

Grade:

Extension Grade or Thermocuple Grade

temperature range, deg. c

-50  to  +400

type of coductor:

K, J, T, E, N, S, R, KX, JX, TX, EX, NX, SX, RX

number of conductors:

1,2,3,4,6

Conductor type

Strand or Solid

material of insulation:

fiberglass, telfon, PTFE, PVC, silicone,so on 

material of jacket:

 fiberglass, telfon, PTFE, PVC, silicone,so on 

shielding material:

 Stainless Steel Braid and  Tinned Copper wire braid 

 

 

TypeConductorGradeWorking temperature
Insulation  material
deg.C
SCu, Ni-CuAPVC
-25~70C
B
RCu, Ni-CuASilicone
-60~200C
B
KCu, Ni-Cu/ATelfon
-60~250C
Ni-Cr, Ni-SiB
NCu, Ni-Cu/AFiberglass
-60~500C
Ni-Cr, Ni-SiB
ENi-Cr,Ni-CuAKapton
-60-300C
B
JIron,Ni-CuA


B


TCu, Ni-CuA


B



AWG

Nominal Conductor

Nominal Thickness


Diameter  

mm


mm

Insulation

Jacket

O.D.

14

1.63

0.18

0.25

2.5 x 4.6

16

1.29

0.18

0.25

2.2 x 3.8

16S

1.47

0.18

0.25

2.4 x 4.3

18

1.02

0.18

0.25

1.8 x 3.2

20

0.81

0.15

0.15

1.4 x 2.5

20S

0.97

0.15

0.15

1.5 x 2.7

22

0.64

0.15

0.15

1.2 x 2.2

24

0.51

0.15

0.15

1.0 x 1.7

24S

0.61

0.15

0.15

1.2 x 2.1

26

0.41

0.11

0.15

0.9 x 1.5

28

0.32

0.11

0.15

0.8 x 1.4

30

0.25

0.11

0.15

0.8 x 1.2

HTB1CV8dX2_HK1JjSsziq6ygrVXau.jpg

The thermocouple compensation cables can also be termed as instrumentation cables, since they are used for

 process temperature measurement.

The construction is similar to pair instrumentation cable but the conductor material is different. 

Thermocouples are used in processes to sense temperature and is connected to the pyrometers for indication 

and control.

The thermocouple and pyrometer are electrically conducted by thermocouple extension cables / thermocouple 

compensating cables.

The conductors used for these thermocouple cables are required to have similar thermo-electric (emf) properties 

as that of the thermocouple used for sensing the temperature.

 

Our factory mainly manufacture type KX,NX,EX,JX,NC,TX,SC/RC,KCA,KCB  compensating wire for 

thermocouple, and they are used in temperature measurement instruments and cables.  

The representing of the comp. wire: thermocouple code+C/X , e.g. SC, KX

X: Short for extension, means that the compensation wire's alloy is as the same as the the alloy of the 

thermocouple

C: Short for compensation, means that the compensation wire's alloy has similar characters with the

 thermocouple's alloy in a certain temperature range.


Online Inquiry